pvc Box

PVC 4-Gang Box 60 cu.in.

Four gang PVC box for large device installations.

Quick answer

A PVC 4-Gang Box 60 cu.in. (60 cu.in.) holds 26 × 12 AWG or 30 × 14 AWG conductors in a bare box under NEC 314.16.

Subtract two allowances for each device or strap, one for all internal clamps, one for one to four entering equipment grounding conductors plus one-quarter for each additional one (NEC 2023 314.16(B)(5)), and one for each type of support fitting. Grounding rule and edition examples →

60

cu.in. Volume

30

Max 14 AWG

26

Max 12 AWG

7-1/2" x 3-1/4" x 3"

Dimensions

Conductor Capacity per NEC 314.16

Maximum number of conductors that can fit in this box based on wire gauge (not accounting for devices, clamps, or grounds).

Wire GaugeVolume EachMax Conductors*
18 AWG1.5 cu.in.40
16 AWG1.75 cu.in.34
14 AWG2 cu.in.30
12 AWG2.25 cu.in.26
10 AWG2.5 cu.in.24
8 AWG3 cu.in.20
6 AWG5 cu.in.12

*Theoretical maximum for conductors only. Actual capacity will be less when including devices, clamps, and grounding conductors.

Common Applications

Control panels
Home automation
Media centers

Calculate Box Fill

Use our free calculator to verify NEC 314.16 requirements.

Calculate Box Fill

Similar Box Types