Box Fill Calculator for Electricians
A free NEC 314.16 box fill calculator that itemizes every conductor, device, clamp, grounding, support-fitting, and terminal-block allowance in the breakdown, so you can calculate box fill and compare the calculated volume with your box's usable capacity.
Box Fill Calculator
Calculate electrical box fill requirements per NEC 314.16
Box Fill Calculator Features
A free box fill calculator that shows the full NEC 314.16 volume breakdown component by component, so you can check the result and defend it during layout, inspection, or rework.
NEC 2023 Box Fill Updated
Instant Box Fill Results
100% Free Calculator
Mobile Box Fill Calculator
How the Box Fill Calculator Works
Three simple steps to calculate electrical box fill per NEC 314.16
- 01
Select Box Type
Choose from standard electrical box sizes or enter the manufacturer-marked usable volume in cubic inches for your box fill calculation.
- 02
Add Components
Enter conductors, devices, clamps, and grounding wires for accurate box fill calculation.
- 03
Get Box Fill Results
Instantly see whether the calculated NEC 314.16 volume fits within your box's capacity.
How to Calculate Box Fill by Hand
This worked example uses the calculator's demo setup: a 4" x 2-1/8" square box (30.30 in³) with six 12 AWG conductors, one device yoke, three entering equipment grounding conductors (EGCs) and internal cable clamps. Every allowance uses the 12 AWG volume of 2.25 in³ from Table 314.16(B).
- 314.16(B)(1) Conductors: 6 conductors × 2.25 in³ = 13.50 in³. Each insulated conductor that comes from outside the box and is spliced or terminated inside counts once.
- 314.16(B)(2) Internal cable clamps: one or more clamps count as a single allowance, 1 × 2.25 in³ = 2.25 in³.
- 314.16(B)(3) Support fittings (fixture studs, hickeys): none in this box, 0.00 in³. Each type present would add one allowance.
- 314.16(B)(4) Device yokes: one yoke counts as two allowances, 2 × 2.25 in³ = 4.50 in³.
- 314.16(B)(5) Equipment grounding conductors: 1 to 4 entering EGCs share one allowance, and each EGC beyond four adds one-quarter allowance. Three EGCs = 1 × 2.25 in³ = 2.25 in³ (six EGCs would be 1.5 allowances).
- 314.16(B)(6) Terminal blocks: none in this box, 0.00 in³.
Required volume: 13.50 + 2.25 + 0.00 + 4.50 + 2.25 + 0.00 = 22.50 in³. The box holds 30.30 in³, so the calculated fill uses 74.3% and leaves 7.80 in³. This checks box volume only; confirm the volume marked on your box and verify other installation requirements separately.
Open this example in the calculatorBox Fill Volume Allowance by Wire Size
Each counted allowance uses the volume for the conductor size in this table. Where a rule says to use the largest conductor, use that size.
| Wire size (AWG) | Volume per allowance (in³) | Volume per allowance (cm³) |
|---|---|---|
| 18 AWG | 1.50 | 24.6 |
| 16 AWG | 1.75 | 28.7 |
| 14 AWG | 2.00 | 32.8 |
| 12 AWG | 2.25 | 36.9 |
| 10 AWG | 2.50 | 41.0 |
| 8 AWG | 3.00 | 49.2 |
| 6 AWG | 5.00 | 81.9 |
Source: NEC 2023 Table 314.16(B). Checked 2026-11-21.
Box Fill Calculator FAQ
What is electrical box fill calculation?
Box fill calculation determines whether an electrical box has sufficient volume for all conductors, devices, and fittings per NEC Article 314.16. Our box fill calculator automates the volume arithmetic so you can check a box before you wire it.
Do wire nuts count in box fill calculations?
No, wire nuts (twist-on connectors) do not count toward box fill. The box fill calculator only counts conductors, devices, clamps, and equipment grounding conductors per NEC 314.16.
How does the box fill calculator count ground wires?
Under NEC 2023 314.16(B)(5), one through four entering equipment grounding conductors share one volume allowance based on the largest entering EGC. Each entering EGC beyond four adds one-quarter allowance at that size. Zero entering EGCs require no allowance; same-box bonding pigtails add none.
What changed in NEC 2023 for box fill?
NEC 2023 added 314.16(B)(6) requiring terminal blocks to be counted in box fill calculations. Our box fill calculator uses the NEC 2023 rules, counting terminal blocks based on the largest conductor connected.
Check a Box Before You Wire It
Check the required NEC 314.16 box-fill volume against your box's usable capacity with our free box fill calculator, including the 2023 terminal-block allowance under 314.16(B)(6).
Start Box Fill Calculator