NEC Code

Grounding Conductor Box Fill: Counts, Pigtails and Examples

By Hommer ZhaoPublished April 15, 20249 min readUpdated Oct 30, 2026

NEC 2023: 0 entering EGCs = no allowance; 1–4 = one allowance; each beyond four adds ¼ allowance, all at the largest entering EGC size. Same-box bonding pigtails add none.

How ground wires count in box fill

Under NEC 2023 314.16(B)(5), up to four equipment grounding conductors (EGCs) entering a box share one volume allowance based on the largest entering EGC. Each additional entering EGC beyond four adds a quarter allowance at that same size. Grounds count; they are not ignored.

Two 12/2 cables, one receptacle yoke, grounds, and an internal clamp require 18.00 cu. in. Without the internal clamp, the same inventory requires 15.75 cu. in.

NEC 2020 vs. 2023: what changed in ground-wire counting

Pre-2020 rules generally grouped EGCs into one allowance regardless of count, with an additional allowance for a separate isolated-ground set. NEC 2020 introduced the four-conductor threshold and quarter increments and removed that separate-set provision; its wording included equipment bonding jumpers. NEC 2023 clarified the entering-EGC basis and removed the bonding-jumper wording. Same-box bonding jumpers do not add entering EGCs. This guide uses NEC 2023 for ordinary cable and raceway inventories; special luminaire-canopy exceptions are outside these examples. Check the adopted edition and local amendments.

The NFPA committee revision and explanation distinguish entering EGCs from bonding jumpers that stay entirely inside the box. This matters when counting a bare-wire bundle with several short pigtails.

Isolated-ground receptacles are an edition issue

NEC 250.146(D) addresses isolated-ground receptacles. It does not mean every isolated-ground EGC adds a quarter allowance. Under NEC 2023 314.16(B)(5), include those entering EGCs in the total and apply the increment only after four. Pre-2020 editions had separate language for an additional isolated-ground set.

Leviton's code-change guide explains the change that removed the need for that separate isolated-ground provision. Do not combine the old separate-set rule with the newer quarter-increment rule.

Five or more ground wires: exact volume before rounding

For 12 AWG EGCs alone, each allowance is 2.25 in³. Five entering grounds require (1 + 1/4) x 2.25 = 2.8125 in³; six require (1 + 2/4) x 2.25 = 3.375 in³. These are grounding subtotals, not complete box totals. With ten insulated 12 AWG conductors, five entering grounds and no other counted items, the total is 22.50 + 2.8125 = 25.3125 in³. A 24.75 in³ box fails; a 25.3125 in³ capacity passes exactly; 25.31 in³ is still too small. The calculator now keeps these fractions through the capacity comparison.

Ground-wire fill by count and gauge

Grounding subtotals below are calculated with the site's box-fill engine using Table 314.16(B) volumes and the NEC 2023 entering-EGC rule. Use the largest entering EGC gauge for the column; wholly internal bonding jumpers and pigtails add none. Add the other counted categories for a complete box total.

Grounding volume only (cu. in.)
Entering EGCs14 AWG12 AWG10 AWG
00.000.000.00
1–42.002.252.50
52.502.81253.125
63.003.3753.75

What to count: entering grounds, pigtails, neutrals, yokes and clamps

  • NEC 314.16(B)(1): A conductor that stays entirely inside the box adds no conductor allowance. A same-box grounding pigtail to a device or bonding jumper to a metal box is not another entering EGC.
  • NEC 314.16(B)(1): Count each entering hot or neutral that terminates or is spliced once, at its own wire size. A neutral is not part of the equipment-grounding group.
  • NEC 314.16(B)(4): A device yoke adds 2 allowances based on the largest conductor connected to it. The grounding allowance does not replace the yoke allowance.
  • NEC 314.16(B)(2): One or more internal cable clamps add 1 allowance based on the largest conductor present. A clamping mechanism outside the box adds no internal-clamp allowance.

Bare and green insulated EGCs follow the same counting rule. Ordinary splice connectors have no separate allowance in these inventories, but connectors, pigtails, and conductor bends still need physical room. See metal-box bonding and pigtails for the distinction between bonding and entering-conductor counts.

Six box-fill inventories: inputs, subtotals and required volume

The volume per allowance in Table 314.16(B)(1) is 2.00 cu. in. for 14 AWG, 2.25 for 12 AWG, and 2.50 for 10 AWG. The largest entering EGC determines the ground-group value.

Calculated on 2026-10-30 with the site's box-fill engine (calculateBoxFill). These are selected hypothetical teaching inventories, with inputs and outputs shown below.

Each cable in the uniform-size rows contains a black and a white insulated conductor plus a same-gauge bare ground. All insulated conductors enter and terminate or are spliced. Yoke connections match the cable gauge. No support fittings, terminal blocks, long unbroken loops, or other volume-counted items are present. The metal-box row adds only same-gauge, same-box grounding pigtails.

The calculator has a single wire-gauge input and applies the entering-EGC count rule, including quarter allowances after four. The mixed-size row uses separate engine calls for insulated conductors, the yoke, the clamp, and the ground group, then adds their volumes; it is not a single mixed-gauge calculator entry.

The final column is the smallest passing volume in the engine's standard-box list across different shapes. It is a volume-only lookup, not a product recommendation. Verify actual marked volume, device gangs, cover compatibility, and physical fit.

Scroll horizontally to see every subtotal and box capacity →. Keyboard: focus the table, then use the arrow keys.

InventoryInsulated + yoke + clamp + ground (cu. in.)Required cu. in.Smallest standard volume that passes (cu. in.)
One 14/2 cable; one switch yoke; internal clamp; one entering ground4.00 + 4.00 + 2.00 + 2.0012.0012.5
Two 12/2 cables; one receptacle yoke; no internal clamp; two entering grounds9.00 + 4.50 + 0.00 + 2.2515.7518.0
Two 12/2 cables; one receptacle yoke; internal clamp; two entering grounds9.00 + 4.50 + 2.25 + 2.2518.0018.0
Three 12/2 cables; no yoke; internal clamp; three entering grounds13.50 + 0.00 + 2.25 + 2.2518.0018.0
Two 12/2 cables; one receptacle yoke; internal clamp; two entering grounds; same-box device and metal-box pigtails9.00 + 4.50 + 2.25 + 2.2518.0018.0
Four entering 12 AWG insulated conductors; one yoke with only 12 AWG connections; internal clamp; one entering 12 AWG EGC and one entering 10 AWG EGC9.00 + 4.50 + 2.50 + 2.5018.5021.0

Worked examples: check the ground group against the whole box

Hypothetical: a single-cable lighting switch box

One 14/2 cable supplies 2 insulated conductors and one entering ground. Add one switch yoke and an internal clamp: 2 + 2 + 1 + 1 = 6 allowances. At 14 AWG, 6 x 2.00 = 12.00 cu. in. A box marked 14.0 cu. in. has 14.00 - 12.00 = 2.00 cu. in. of calculated margin.

Hypothetical: feed-in and feed-out at a receptacle

Two 12/2 cables bring 4 insulated conductors and two entering grounds. One receptacle yoke, an internal clamp, and the grouped grounds give 4 + 2 + 1 + 1 = 8 allowances: 8 x 2.25 = 18.00 cu. in. Removing the internal clamp allowance gives 18.00 - 2.25 = 15.75 cu. in. A box marked 18.0 cu. in. has 0.00 cu. in. of calculated margin with the clamp.

A GFCI body does not create another grounding allowance. Check its depth and conductor arrangement separately; the GFCI box-fill guide explains the LINE and LOAD inventory.

Hypothetical: bonding a metal box and the device

Start with the clamped two-cable 12 AWG receptacle inventory above. Add a grounding pigtail to the device and a bonding jumper to the metal box, both of the same gauge and entirely inside the box. The entering EGC count stays at 2; the ground allowance stays at 2.25 cu. in. and total fill stays at 18.00 cu. in. This volume calculation does not establish that a particular bonding connection is acceptable.

Hypothetical: a larger entering ground in a mixed-size box

Assume four entering 12 AWG insulated conductors, one yoke with only 12 AWG connections, an internal clamp, and two entering EGCs, one 12 AWG and one 10 AWG. The larger EGC bonds the box; it is not connected to the yoke. The insulated conductors use 4 x 2.25 = 9.00 cu. in.; the yoke uses 2 x 2.25 = 4.50 cu. in. The clamp and ground group each use 2.50 cu. in. Total: 9.00 + 4.50 + 2.50 + 2.50 = 18.50 cu. in. A box marked 18.0 cu. in. is short by 0.50 cu. in.; a box marked 21.0 cu. in. has 2.50 cu. in. of calculated margin.

That is an explicitly defined volume inventory, not a specification for conductor sizing or circuit connections. For other mixes, keep the wire-size ledger separate by conductor and fitting category.

Marked box capacity and usable space are separate checks

Compare the complete required volume with the box's marked capacity or the applicable standard-metal-box table. A passing arithmetic result does not establish that a device can be installed without crowding or damaging conductors. Check the actual device body, connector clearance, conductor folding, and manufacturer instructions. Extra depth can help, but the capacity used in the calculation must be documented.

Ground wire box-fill FAQ

Do all ground wires count as one conductor for box fill?

Under NEC 2023 314.16(B)(5), up to four equipment grounding conductors entering a box share one allowance based on the largest entering EGC. Each entering EGC beyond four adds a quarter allowance at that same size. The unlimited all-grounds-count-once shortcut does not describe this edition.

Do bare and green insulated ground wires count differently?

No. Both count as equipment grounding conductors when they serve that function. Count the entering EGCs and use the largest entering EGC size; insulation color does not create a separate box-fill category.

Does a metal-box bonding jumper or device grounding pigtail add fill?

A jumper or pigtail wholly inside the box adds no entering conductor to the count. In the example with two 12/2 cables, one receptacle yoke, and an internal clamp, adding same-box grounding pigtails leaves the total at 18.00 cu. in. The entering grounds still count, and the connectors still need physical space.

What if the box contains both 12 AWG and 10 AWG grounds?

For up to four entering EGCs, use one 10 AWG grounding allowance: 2.50 cu. in. Keep insulated-conductor and yoke volumes separate. The worked mixed-size inventory needs 18.50 cu. in.; its larger ground does not turn every insulated conductor into 10 AWG.

Does an isolated ground automatically add a quarter allowance?

No. In NEC 2023 314.16(B)(5), the quarter increment applies to each entering EGC beyond four. Include the isolated-ground EGCs in that count. Section 250.146(D) addresses isolated-ground receptacles; it does not impose a blanket quarter-allowance surcharge. Pre-2020 editions treated the additional isolated-ground set separately.

Are neutrals counted with the ground bundle?

No. Each entering neutral that terminates or is spliced in the box counts under NEC 314.16(B)(1), just like an entering hot conductor. Do not put neutrals into the grouped EGC allowance, and do not confuse this volume calculation with ampacity-adjustment rules.

Code sources and related box-fill references

Use the adopted NFPA 70 edition for the governing text. The linked committee document explains the entering-conductor distinction; the manufacturer code-change guide explains the isolated-ground history.

Calculate single-gauge box fill: inputs and limits

Enter the marked box volume, a single wire gauge, insulated-conductor and device-yoke counts, internal clamps, entering EGCs, support-fitting types, and terminal block assemblies. All conductors, including EGCs, must match the selected gauge; the engine includes quarter allowances after four entering EGCs. Exclude wholly internal bonding jumpers and pigtails from the entering count. Keep a separate category-by-category ledger for mixed sizes. Compare the full required volume with marked capacity, then assess physical fit and the applicable installation requirements separately.

Open the Box Fill Calculator

Tags:

groundingequipment ground314.16(B)(5)ground wire