PVC Single Gang Box 20 cu.in.
Larger PVC single gang box for installations with more conductors.
20
cu.in. Volume
10
Max 14 AWG
9
Max 12 AWG
3" x 2-1/4" x 4"
Dimensions
Conductor Capacity per NEC 314.16
Maximum number of conductors that can fit in this 20 cu.in. box based on wire gauge (not accounting for devices, clamps, or grounds).
| Wire Gauge | Volume Each | Max Conductors* |
|---|---|---|
| 18 AWG | 1.5 cu.in. | 13 |
| 16 AWG | 1.75 cu.in. | 11 |
| 14 AWG | 2 cu.in. | 10 |
| 12 AWG | 2.25 cu.in. | 8 |
| 10 AWG | 2.5 cu.in. | 8 |
| 8 AWG | 3 cu.in. | 6 |
| 6 AWG | 5 cu.in. | 4 |
*Theoretical maximum for conductors only. Actual capacity will be less when including devices, clamps, and grounding conductors.
Common Applications
Calculate Box Fill for PVC Single Gang Box 20 cu.in.
Use our free calculator to verify your PVC Single Gang Box 20 cu.in. meets NEC 314.16 requirements.
Open Box Fill CalculatorSimilar Box Types
About the PVC Single Gang Box 20 cu.in.
The PVC Single Gang Box 20 cu.in. provides 20 cubic inches of volume for electrical connections. This pvc box is commonly used for residential with multiple circuits, deep wall installations. With dimensions of 3" x 2-1/4" x 4", it offers adequate space for most residential and light commercial applications.
Box Fill Calculation Example
For a typical installation using 14 AWG conductors:
- Box volume: 20 cu.in.
- 14 AWG conductor volume: 2.00 cu.in. each
- Maximum conductors (theoretical): 10
Remember to account for devices (2× conductor volume each), internal clamps (1× conductor volume), and equipment grounding conductors (1× conductor volume for all grounds combined).
Practical Example: Receptacle Installation
Installing a duplex receptacle with two 14/2 NM cables in this box:
- 4 × 14 AWG conductors = 4 × 2.00 = 8.00 cu.in.
- 2 × grounds (count as 1) = 1 × 2.00 = 2.00 cu.in.
- Internal clamps = 1 × 2.00 = 2.00 cu.in.
- 1 × receptacle = 2 × 2.00 = 4.00 cu.in.
- Total: 16.00 cu.in.
Result: 16.00 cu.in. ≤ 20 cu.in. = COMPLIANT