NEC 314.16 Complete Guide: Box Fill Calculations Explained

Published January 15, 202412 min readUpdated Nov 1, 2024

NEC 314.16 establishes the requirements for sizing electrical boxes. This comprehensive guide covers everything you need to know about box fill calculations, from conductor volume allowances to the latest NEC 2023 changes.

What is NEC 314.16?

Article 314.16 of the National Electrical Code (NEC) specifies the minimum volume requirements for electrical outlet boxes, device boxes, and junction boxes. The primary purpose is to ensure adequate space for conductors, splices, and devices while preventing overcrowding that could lead to damaged insulation or fire hazards.

Why Box Fill Calculations Matter

Proper box fill calculations are essential for several reasons:

  • Safety: Overcrowded boxes can cause overheating and insulation damage
  • Code Compliance: Inspectors will fail installations that exceed fill limits
  • Workmanship: Adequate space allows for neat, professional connections
  • Future Modifications: Proper sizing leaves room for circuit additions

Understanding Volume Allowances

NEC Table 314.16(B) provides the volume allowance for each conductor based on its AWG size:

Wire Size (AWG)Volume (cu. in.)
181.50
161.75
142.00
122.25
102.50
83.00
65.00

For complete wire gauge information, see our wire gauge reference guide.

Box Fill Calculation Components

A complete box fill calculation includes:

1. Conductor Fill [314.16(B)(1)]

Count each conductor that originates outside the box and terminates or is spliced within the box. Conductors passing through without splice or termination count once per conductor.

2. Clamp Fill [314.16(B)(2)]

One or more internal cable clamps require a single volume allowance based on the largest conductor present. External clamps do not require an allowance.

3. Support Fittings Fill [314.16(B)(3)]

Fixture studs and hickeys require one conductor volume allowance based on the largest conductor.

4. Device Fill [314.16(B)(4)]

Each device yoke or strap requires a double volume allowance (2×) based on the largest conductor connected to that device. This applies to switches, receptacles, dimmers, and similar devices. Learn more in our device fill calculations guide.

5. Equipment Grounding Conductor Fill [314.16(B)(5)]

All equipment grounding conductors count as a single conductor based on the largest ground entering the box. This is one of the most commonly misunderstood provisions—all grounds combined count as just one conductor. Read our detailed grounding conductor guide.

6. Terminal Block Fill [314.16(B)(6)] - NEC 2023

The 2023 NEC added requirements for terminal blocks. Volume allowances are calculated based on conductors connected to the terminal block. See our NEC 2023 changes article for details.

Step-by-Step Calculation Example

Let's calculate box fill for a typical outlet box:

  • Box: 4" square × 1-1/2" deep (21 cu.in.)
  • 4 × 14 AWG conductors (2 cables, each with hot and neutral)
  • 2 × 14 AWG ground wires
  • 1 duplex receptacle
  • Internal cable clamps

Calculation:

  • Conductors: 4 × 2.00 = 8.00 cu.in.
  • Clamps: 1 × 2.00 = 2.00 cu.in.
  • Grounds: 1 × 2.00 = 2.00 cu.in.
  • Device: 2 × 2.00 = 4.00 cu.in.
  • Total: 16.00 cu.in.

Result: 16.00 cu.in. ≤ 21.00 cu.in. = COMPLIANT

Common Mistakes to Avoid

Learn more about these in our common mistakes guide:

  • Counting ground wires individually (they should be counted as one)
  • Forgetting to count internal clamps
  • Using the wrong conductor size for device fill calculations
  • Not counting conductors that pass through without terminating
  • Ignoring pigtails that originate outside the box

Choosing the Right Box

Browse our comprehensive electrical box reference to find the perfect box for your installation, with detailed specifications for each type.

Use Our Free Calculator

Manually calculating box fill can be error-prone. Our free box fill calculator automatically applies all NEC 314.16 requirements and gives you instant compliance verification.

Tags:

NEC 314.16box fillelectrical codeconductor volume