Calculadora NEC 314.16 Gratuita

Calculadora de Enchimento de Caixa para Eletricistas

Uma calculadora gratuita de ocupação de caixas elétricas conforme o NEC 314.16 que detalha o volume atribuído a cada condutor, dispositivo, abraçadeira, condutor de aterramento, acessório de suporte e bloco de terminais, para calcular a ocupação e confirmar a conformidade da instalação.

Calculadora de Enchimento de Caixa

Calculate electrical box fill requirements per NEC 314.16

Your box & components
01 Choose your box
Box capacity— in³
02Count what’s insideWire gauge
Same wire gauge throughout, including grounds
2.25 in³ per allowance
Exclude grounds
Count mounting straps
Entering the box
Inside the box only
Updates as you edit. Grounds are counted separately.

Box Fill Calculator

Por Que Usar Nossa Calculadora de Enchimento?

Uma calculadora gratuita de ocupação de caixas que apresenta o cálculo completo do volume conforme o NEC 314.16, componente por componente, para conferir o resultado e justificá-lo durante o planejamento, a inspeção ou o retrabalho.

Atualizada para NEC 2023

Nossa calculadora acompanha as exigências mais recentes do Código Elétrico Nacional, incluindo blocos terminais conforme 314.16(B)(6).

Resultados Instantâneos

Obtenha cálculos precisos de enchimento em segundos, com detalhamento de volume para cada componente.

100% Gratuita

Sem cadastro. Use nossa calculadora de enchimento gratuitamente sempre que precisar de cálculos exatos.

Funciona no Celular

Calcule o enchimento de caixa em qualquer dispositivo. Ideal para cálculos na obra.

Como a Calculadora de Enchimento Funciona

Três passos simples para calcular o enchimento de caixas elétricas conforme NEC 314.16

  1. 01

    Selecione o Tipo de Caixa

    Escolha entre tamanhos padrão de caixas elétricas ou insira dimensões personalizadas para o cálculo.

  2. 02

    Adicione Componentes

    Informe condutores, dispositivos, braçadeiras e fios de aterramento para um cálculo preciso.

  3. 03

    Veja o Resultado

    Confira instantaneamente se sua caixa elétrica atende aos requisitos de enchimento do NEC 314.16.

How to Calculate Box Fill by Hand

This worked example uses the calculator's demo setup: a 4" x 2-1/8" square box (30.30 in³) with six 12 AWG conductors, one device yoke, three entering equipment grounding conductors (EGCs) and internal cable clamps. Every allowance uses the 12 AWG volume of 2.25 in³ from Table 314.16(B).

  1. 314.16(B)(1) Conductors: 6 conductors × 2.25 in³ = 13.50 in³. Each insulated conductor that comes from outside the box and is spliced or terminated inside counts once.
  2. 314.16(B)(2) Internal cable clamps: one or more clamps count as a single allowance, 1 × 2.25 in³ = 2.25 in³.
  3. 314.16(B)(3) Support fittings (fixture studs, hickeys): none in this box, 0.00 in³. Each type present would add one allowance.
  4. 314.16(B)(4) Device yokes: one yoke counts as two allowances, 2 × 2.25 in³ = 4.50 in³.
  5. 314.16(B)(5) Equipment grounding conductors: 1 to 4 entering EGCs share one allowance, and each EGC beyond four adds one-quarter allowance. Three EGCs = 1 × 2.25 in³ = 2.25 in³ (six EGCs would be 1.5 allowances).
  6. 314.16(B)(6) Terminal blocks: none in this box, 0.00 in³.

Required volume: 13.50 + 2.25 + 0.00 + 4.50 + 2.25 + 0.00 = 22.50 in³. The box holds 30.30 in³, so the calculated fill uses 74.3% and leaves 7.80 in³. This checks box volume only; confirm the volume marked on your box and verify other installation requirements separately.

Open this example in the calculator

Box Fill Volume Allowance by Wire Size

Each counted allowance uses the volume for the conductor size in this table. Where a rule says to use the largest conductor, use that size.

Wire size (AWG)Volume per allowance (in³)Volume per allowance (cm³)
18 AWG1.5024.6
16 AWG1.7528.7
14 AWG2.0032.8
12 AWG2.2536.9
10 AWG2.5041.0
8 AWG3.0049.2
6 AWG5.0081.9

Source: NEC 2023 Table 314.16(B). Checked 2026-11-21.

Perguntas Frequentes sobre Enchimento de Caixa

O que é o cálculo de enchimento de caixa elétrica?

O cálculo de enchimento determina se uma caixa elétrica possui volume suficiente para todos os condutores, dispositivos e acessórios conforme o NEC Artigo 314.16. Nossa calculadora automatiza esse processo para garantir instalações seguras e prevenir superaquecimento.

Conectores de torção contam no enchimento de caixa?

Não. Conectores de torção (wire nuts) não contam no enchimento de caixa. A calculadora considera apenas condutores, dispositivos, braçadeiras e condutores de aterramento conforme NEC 314.16.

Como a calculadora contabiliza os fios terra?

Todos os condutores de aterramento em uma caixa contam como um único volume de condutor, baseado no maior condutor de aterramento que entra na caixa, conforme NEC 314.16(B)(5).

Como a calculadora contabiliza os fios terra? (English page)

O que mudou no NEC 2023 para enchimento de caixa?

O NEC 2023 adicionou o item 314.16(B)(6), exigindo que blocos terminais sejam contabilizados no cálculo de enchimento. Nossa calculadora está totalmente atualizada, calculando blocos terminais com base no maior condutor conectado.

Pronto para Calcular o Enchimento de Caixa?

Verifique se suas instalações elétricas atendem ao NEC 314.16 com nossa calculadora gratuita de ocupação de caixas, incluindo o volume dos blocos de terminais previsto em 314.16(B)(6) da edição de 2023.

Iniciar Calculadora de Enchimento