Single Gang Device Box 18 cu.in.
Metal single gang device box with 18 cubic inch capacity. Ideal for residential and light commercial switch and receptacle installations.
18
cu.in. Volume
9
Max 14 AWG
8
Max 12 AWG
3" x 2" x 3-1/2"
Dimensions
Conductor Capacity per NEC 314.16
Maximum number of conductors that can fit in this 18 cu.in. box based on wire gauge (not accounting for devices, clamps, or grounds).
| Wire Gauge | Volume Each | Max Conductors* |
|---|---|---|
| 18 AWG | 1.5 cu.in. | 12 |
| 16 AWG | 1.75 cu.in. | 10 |
| 14 AWG | 2 cu.in. | 9 |
| 12 AWG | 2.25 cu.in. | 8 |
| 10 AWG | 2.5 cu.in. | 7 |
| 8 AWG | 3 cu.in. | 6 |
| 6 AWG | 5 cu.in. | 3 |
*Theoretical maximum for conductors only. Actual capacity will be less when including devices, clamps, and grounding conductors.
Common Applications
Calculate Box Fill for Single Gang Device Box 18 cu.in.
Use our free calculator to verify your Single Gang Device Box 18 cu.in. meets NEC 314.16 requirements.
Open Box Fill CalculatorSimilar Box Types
About the Single Gang Device Box 18 cu.in.
The Single Gang Device Box 18 cu.in. provides 18 cubic inches of volume for electrical connections. This metal box is commonly used for light switches, outlets, receptacles, gfci installations. With dimensions of 3" x 2" x 3-1/2", it offers adequate space for most residential and light commercial applications.
Box Fill Calculation Example
For a typical installation using 14 AWG conductors:
- Box volume: 18 cu.in.
- 14 AWG conductor volume: 2.00 cu.in. each
- Maximum conductors (theoretical): 9
Remember to account for devices (2× conductor volume each), internal clamps (1× conductor volume), and equipment grounding conductors (1× conductor volume for all grounds combined).
Practical Example: Receptacle Installation
Installing a duplex receptacle with two 14/2 NM cables in this box:
- 4 × 14 AWG conductors = 4 × 2.00 = 8.00 cu.in.
- 2 × grounds (count as 1) = 1 × 2.00 = 2.00 cu.in.
- Internal clamps = 1 × 2.00 = 2.00 cu.in.
- 1 × receptacle = 2 × 2.00 = 4.00 cu.in.
- Total: 16.00 cu.in.
Result: 16.00 cu.in. ≤ 18 cu.in. = COMPLIANT
Related Resources
- Complete NEC 314.16 Guide
- How to Calculate Box Fill Step-by-Step
- Junction Box Sizing Guide
- Wire Gauge Volume Chart
- NEC 314.16 Code Reference
Need Help with Box Fill?
Our free box fill calculator automatically calculates all components per NEC 314.16, ensuring your installation is code compliant.