metal Box

4" Square x 2-1/8" Deep

Deep 4-inch square electrical box ideal for multiple conductors and complex wiring configurations.

How many wires fit in a 4 square box, 2-1/8 inches deep?

This box is marked 30.3 cu.in. and holds 15 × 14 AWG, 13 × 12 AWG or 12 × 10 AWG conductors when nothing else is counted. With one allowance for one through four entering EGCs under NEC 2023, that drops to 14 / 12 / 11; add internal clamps and it is 13 / 11 / 10.

Per NEC 2023 314.16(B): each insulated conductor entering the box is 1 allowance, 1–4 entering EGCs share 1 allowance (add ¼ for each beyond four at the largest entering EGC size), all internal clamps together are 1, and each device yoke is 2. Grounding rule and edition examples →

30.3

cu.in. Volume

15

Max 14 AWG

13

Max 12 AWG

4" x 4" x 2-1/8"

Dimensions

Conductor Capacity per NEC 314.16

Maximum number of conductors that can fit in this box based on wire gauge (not accounting for devices, clamps, or grounds).

Wire GaugeVolume EachMax Conductors*
18 AWG1.5 cu.in.20
16 AWG1.75 cu.in.17
14 AWG2 cu.in.15
12 AWG2.25 cu.in.13
10 AWG2.5 cu.in.12
8 AWG3 cu.in.10
6 AWG5 cu.in.6

*Theoretical maximum for conductors only. Actual capacity will be less when including devices, clamps, and grounding conductors.

Wires per gauge in a 4" x 4" x 2-1/8" box (30.3 cu.in.)

Each cell is the most insulated conductors of that gauge the box can hold, found by running the site calculator engine (30.3 cu.in. box, conductor allowance from Table 314.16(B)) until the required volume would exceed the box volume. The first column counts conductors only; each later column adds the deductions named in its heading. A 12/2 cable has 2 insulated conductors and 1 entering EGC. The table assumes 1–4 entering EGCs for the ground deduction; larger groups need additional quarter allowances and lower the insulated-conductor capacity.

Maximum conductors by wire gauge for a 4 inch square box 2-1/8 inches deep
Wire gaugeAllowance eachConductors only+ ground allowance+ ground + clamps+ ground + clamps + 1 device+ ground + clamps + 2 devices
14 AWG2.00 cu.in.151413119
12 AWG2.25 cu.in.13121197
10 AWG2.50 cu.in.12111086
8 AWG3.00 cu.in.109864
6 AWG5.00 cu.in.65420

Counts are for a single gauge per box and are capacity only; they do not replace conductor-ampacity or derating rules, and the box volume stamped on your box governs.

How the deductions change the count

  • Conductors: 1 allowance for each insulated conductor that comes in from outside and is spliced or terminated in the box (NEC 314.16(B)(1)).
  • Clamps: 1 allowance for all internal cable clamps together (314.16(B)(2)), sized by the largest conductor in the box.
  • Devices: 2 allowances for each yoke or strap, sized by the largest conductor connected to it (314.16(B)(4)).
  • Grounds: NEC 2023 uses 1 allowance for 1–4 entering EGCs plus ¼ for each beyond four, based on the largest entering EGC (314.16(B)(5)).

Worked examples (engine totals)

12/2 cables, internal clamps, one entering EGC per cable. 5 cables = 10 conductors, plus 1 clamp and 1.25 grounding allowances = 12.25 allowances × 2.25 = 27.5625 cu.in. of 30.3, so it fits. A 6th cable would make 32.625 cu.in., which does not.

Same box with one switch or receptacle. The device adds 2 allowances: 4 cables = 8 conductors + 1 clamp + 1 grounding allowances + 2 device = 12 allowances × 2.25 = 27.00 cu.in. and fits. A 5th cable would make 32.0625 cu.in., which does not.

Mixed 14 AWG and 12 AWG (three 14/2 and two 12/2 cables, internal clamps). Each conductor counts at its own size: 6 × 2.00 = 12.00 cu.in. for the 14 AWG and 4 × 2.25 = 9.00 cu.in. for the 12 AWG. The clamp uses 12 AWG volume and the five entering grounds use 1.25 allowances at the largest entering EGC size, 12 AWG: 2.25 + 2.8125 = 5.0625 cu.in. Total 26.0625 cu.in., leaving 4.2375 cu.in. in a 30.3 cu.in. box. To compare with the table, divide by 2.25: this load uses 11.5833 of the 13.4667 twelve-gauge slots the box has, so a 14 AWG conductor takes 2.00 / 2.25 = 0.89 of a 12 AWG slot. These are hypothetical cables chosen to show the arithmetic; count your own conductors on the job.

FAQ

How many 12 AWG wires can go in a 4 inch square box that is 2-1/8 inches deep?

The box is marked 30.3 cu. in. and each 12 AWG conductor takes 2.25 cu. in., so 13 conductors fit with nothing else counted. Counting one allowance for one through four entering EGCs under NEC 2023 leaves 12, and adding one for internal cable clamps leaves 11.

Do the ground wires count toward the wire limit in a 4 square box?

Under NEC 2023, one through four entering EGCs share one allowance at the largest entering EGC size; each entering EGC beyond four adds one-quarter allowance at that size. For one through four entering EGCs in this box, one ground allowance takes the 12 AWG limit from 13 to 12 and the 14 AWG limit from 15 to 14.

How many wires fit if the box also holds a switch or receptacle?

A device (switch or receptacle on a yoke) counts as two allowances of the largest conductor connected to it. With one device, internal clamps and the ground allowance, the box takes 11 x 14 AWG, 9 x 12 AWG or 8 x 10 AWG conductors.

See also: all electrical box sizes, 14 AWG, 12 AWG and 10 AWG wire pages, the box fill chart by gauge and the complete NEC 314.16 guide.

Common Applications

High-capacity junction
Multiple circuit connections
Commercial installations

Calculate Box Fill

Use our free calculator to verify NEC 314.16 requirements.

Calculate Box Fill

Similar Box Types