pvc Box

PVC 3-Gang Box 44 cu.in.

Triple gang PVC box for multiple device installations.

44

cu.in. Volume

22

Max 14 AWG

19

Max 12 AWG

5-3/4" x 3-1/4" x 3"

Dimensions

Conductor Capacity per NEC 314.16

Maximum number of conductors that can fit in this 44 cu.in. box based on wire gauge (not accounting for devices, clamps, or grounds).

Wire GaugeVolume EachMax Conductors*
18 AWG1.5 cu.in.29
16 AWG1.75 cu.in.25
14 AWG2 cu.in.22
12 AWG2.25 cu.in.19
10 AWG2.5 cu.in.17
8 AWG3 cu.in.14
6 AWG5 cu.in.8

*Theoretical maximum for conductors only. Actual capacity will be less when including devices, clamps, and grounding conductors.

Common Applications

Triple switch installations
Media centers

Calculate Box Fill for PVC 3-Gang Box 44 cu.in.

Use our free calculator to verify your PVC 3-Gang Box 44 cu.in. meets NEC 314.16 requirements.

Open Box Fill Calculator

Similar Box Types

About the PVC 3-Gang Box 44 cu.in.

The PVC 3-Gang Box 44 cu.in. provides 44 cubic inches of volume for electrical connections. This pvc box is commonly used for triple switch installations, media centers. With dimensions of 5-3/4" x 3-1/4" x 3", it offers adequate space for most residential and light commercial applications.

Box Fill Calculation Example

For a typical installation using 14 AWG conductors:

  • Box volume: 44 cu.in.
  • 14 AWG conductor volume: 2.00 cu.in. each
  • Maximum conductors (theoretical): 22

Remember to account for devices (2× conductor volume each), internal clamps (1× conductor volume), and equipment grounding conductors (1× conductor volume for all grounds combined).

Practical Example: Receptacle Installation

Installing a duplex receptacle with two 14/2 NM cables in this box:

  • 4 × 14 AWG conductors = 4 × 2.00 = 8.00 cu.in.
  • 2 × grounds (count as 1) = 1 × 2.00 = 2.00 cu.in.
  • Internal clamps = 1 × 2.00 = 2.00 cu.in.
  • 1 × receptacle = 2 × 2.00 = 4.00 cu.in.
  • Total: 16.00 cu.in.

Result: 16.00 cu.in. 44 cu.in. = COMPLIANT