metal Box

3-Gang Device Box 2-3/4" Deep

Triple gang device box for multiple device installations.

42

cu.in. Volume

21

Max 14 AWG

18

Max 12 AWG

5-5/8" x 3" x 2-3/4"

Dimensions

Conductor Capacity per NEC 314.16

Maximum number of conductors that can fit in this 42 cu.in. box based on wire gauge (not accounting for devices, clamps, or grounds).

Wire GaugeVolume EachMax Conductors*
18 AWG1.5 cu.in.28
16 AWG1.75 cu.in.24
14 AWG2 cu.in.21
12 AWG2.25 cu.in.18
10 AWG2.5 cu.in.16
8 AWG3 cu.in.14
6 AWG5 cu.in.8

*Theoretical maximum for conductors only. Actual capacity will be less when including devices, clamps, and grounding conductors.

Common Applications

Triple switch panels
Multiple outlet installations

Calculate Box Fill for 3-Gang Device Box 2-3/4" Deep

Use our free calculator to verify your 3-Gang Device Box 2-3/4" Deep meets NEC 314.16 requirements.

Open Box Fill Calculator

Similar Box Types

About the 3-Gang Device Box 2-3/4" Deep

The 3-Gang Device Box 2-3/4" Deep provides 42 cubic inches of volume for electrical connections. This metal box is commonly used for triple switch panels, multiple outlet installations. With dimensions of 5-5/8" x 3" x 2-3/4", it offers adequate space for most residential and light commercial applications.

Box Fill Calculation Example

For a typical installation using 14 AWG conductors:

  • Box volume: 42 cu.in.
  • 14 AWG conductor volume: 2.00 cu.in. each
  • Maximum conductors (theoretical): 21

Remember to account for devices (2× conductor volume each), internal clamps (1× conductor volume), and equipment grounding conductors (1× conductor volume for all grounds combined).

Practical Example: Receptacle Installation

Installing a duplex receptacle with two 14/2 NM cables in this box:

  • 4 × 14 AWG conductors = 4 × 2.00 = 8.00 cu.in.
  • 2 × grounds (count as 1) = 1 × 2.00 = 2.00 cu.in.
  • Internal clamps = 1 × 2.00 = 2.00 cu.in.
  • 1 × receptacle = 2 × 2.00 = 4.00 cu.in.
  • Total: 16.00 cu.in.

Result: 16.00 cu.in. 42 cu.in. = COMPLIANT