metal Box
2-Gang Device Box 2-3/4" Deep
Double gang device box for dual devices or larger equipment.
Quick answer
A 2-Gang Device Box 2-3/4" Deep (28 cu.in.) holds 12 × 12 AWG or 14 × 14 AWG conductors in a bare box under NEC 314.16.
Subtract two allowances for each device or strap, and one for each set of internal clamps, grounding conductors, or support fittings. Run your exact box fill →
28
cu.in. Volume
14
Max 14 AWG
12
Max 12 AWG
4" x 3" x 2-3/4"
Dimensions
Conductor Capacity per NEC 314.16
Maximum number of conductors that can fit in this box based on wire gauge (not accounting for devices, clamps, or grounds).
| Wire Gauge | Volume Each | Max Conductors* |
|---|---|---|
| 18 AWG | 1.5 cu.in. | 18 |
| 16 AWG | 1.75 cu.in. | 16 |
| 14 AWG | 2 cu.in. | 14 |
| 12 AWG | 2.25 cu.in. | 12 |
| 10 AWG | 2.5 cu.in. | 11 |
| 8 AWG | 3 cu.in. | 9 |
| 6 AWG | 5 cu.in. | 5 |
*Theoretical maximum for conductors only. Actual capacity will be less when including devices, clamps, and grounding conductors.
Common Applications
Dual switches
Switch/outlet combo
GFCI installations
Calculate Box Fill
Use our free calculator to verify NEC 314.16 requirements.