电气盒填充计算器 专为电工设计
免费的 NEC 314.16 电气接线盒填充计算器,逐项列出导线、器件、夹具、接地导线、支撑配件和端子排的容积占用量,帮助你计算接线盒填充量并确认安装符合规范。
电气盒填充计算器
Calculate electrical box fill requirements per NEC 314.16
为什么选择我们的电气盒填充计算器?
免费的接线盒填充计算器,按部件完整展示 NEC 314.16 容积计算明细,便于核对结果,并在布置、验收或返工时说明计算依据。
NEC 2023盒填充更新
即时盒填充结果
100%免费计算器
移动端盒填充计算器
电气盒填充计算器使用方法
三个简单步骤计算符合NEC 314.16的电气盒填充
- 01
选择盒子类型
从标准电气盒尺寸中选择或输入自定义尺寸进行盒填充计算。
- 02
添加组件
输入导体、设备、线夹和接地线进行准确的盒填充计算。
- 03
获取盒填充结果
即时查看您的电气盒是否符合NEC 314.16盒填充要求。
How to Calculate Box Fill by Hand
This worked example uses the calculator's demo setup: a 4" x 2-1/8" square box (30.30 in³) with six 12 AWG conductors, one device yoke, three entering equipment grounding conductors (EGCs) and internal cable clamps. Every allowance uses the 12 AWG volume of 2.25 in³ from Table 314.16(B).
- 314.16(B)(1) Conductors: 6 conductors × 2.25 in³ = 13.50 in³. Each insulated conductor that comes from outside the box and is spliced or terminated inside counts once.
- 314.16(B)(2) Internal cable clamps: one or more clamps count as a single allowance, 1 × 2.25 in³ = 2.25 in³.
- 314.16(B)(3) Support fittings (fixture studs, hickeys): none in this box, 0.00 in³. Each type present would add one allowance.
- 314.16(B)(4) Device yokes: one yoke counts as two allowances, 2 × 2.25 in³ = 4.50 in³.
- 314.16(B)(5) Equipment grounding conductors: 1 to 4 entering EGCs share one allowance, and each EGC beyond four adds one-quarter allowance. Three EGCs = 1 × 2.25 in³ = 2.25 in³ (six EGCs would be 1.5 allowances).
- 314.16(B)(6) Terminal blocks: none in this box, 0.00 in³.
Required volume: 13.50 + 2.25 + 0.00 + 4.50 + 2.25 + 0.00 = 22.50 in³. The box holds 30.30 in³, so the calculated fill uses 74.3% and leaves 7.80 in³. This checks box volume only; confirm the volume marked on your box and verify other installation requirements separately.
Open this example in the calculatorBox Fill Volume Allowance by Wire Size
Each counted allowance uses the volume for the conductor size in this table. Where a rule says to use the largest conductor, use that size.
| Wire size (AWG) | Volume per allowance (in³) | Volume per allowance (cm³) |
|---|---|---|
| 18 AWG | 1.50 | 24.6 |
| 16 AWG | 1.75 | 28.7 |
| 14 AWG | 2.00 | 32.8 |
| 12 AWG | 2.25 | 36.9 |
| 10 AWG | 2.50 | 41.0 |
| 8 AWG | 3.00 | 49.2 |
| 6 AWG | 5.00 | 81.9 |
Source: NEC 2023 Table 314.16(B). Checked 2026-11-21.
电气盒填充计算器常见问题
什么是电气盒填充计算?
盒填充计算根据NEC第314.16条确定电气盒是否有足够的体积容纳所有导体、设备和配件。我们的盒填充计算器自动化此过程,确保安装安全并防止过热。
线帽在盒填充计算中是否计入?
不,线帽(旋入式连接器)不计入盒填充。盒填充计算器只计算导体、设备、线夹和设备接地导体,符合NEC 314.16。
盒填充计算器如何计算接地线?
在盒填充计算中,盒子内所有设备接地导体算作单个导体体积,基于进入盒子的最大设备接地导体,符合NEC 314.16(B)(5)。
NEC 2023对盒填充有什么变化?
NEC 2023增加了314.16(B)(6),要求将终端块计入盒填充计算。我们的盒填充计算器已完全更新支持NEC 2023,根据连接的最大导体计算终端块。