18

18 AWG Wire Box Fill

18 AWG conductors are typically used for low-voltage applications and control wiring.

1.5

cu.in. per conductor

24.6

mm³ per conductor

7A

Max Ampacity

Common Applications

Thermostat wiring
Doorbell circuits
Low-voltage controls

Box Capacity for 18 AWG

Maximum number of 18 AWG conductors that fit in common electrical boxes (conductors only, not accounting for devices, clamps, or grounds).

*Theoretical maximum. Use our box fill calculator for actual installation capacity including devices and other fill factors.

Calculate Box Fill with 18 AWG

Enter your 18 AWG conductor count and other components for instant NEC compliance verification.

Open Box Fill Calculator

18 AWG Conductor Volume Allowance

Per NEC Table 314.16(B), 18 AWG conductors require 1.5 cubic inches (24.6 mm³) of box volume each. This volume allowance applies to:

  • Each conductor originating outside the box and terminating or splicing inside
  • Conductors passing through without splice (counted once per conductor)
  • Device fill calculations (based on largest conductor connected)
  • Equipment grounding conductor fill (based on largest ground)

When to Use 18 AWG Wire

18 AWG conductors are rated for 7 amps and commonly used for thermostat wiring, doorbell circuits, low-voltage controls. Always verify conductor sizing meets circuit requirements per NEC Article 310.

Box Fill Calculation Example

For a receptacle installation with two 18/2 NM cables:

  • 4 × 18 AWG conductors = 4 × 1.5 = 6.00 cu.in.
  • 2 × grounds (count as 1) = 1 × 1.5 = 1.5 cu.in.
  • Internal clamps = 1 × 1.5 = 1.5 cu.in.
  • 1 × receptacle = 2 × 1.5 = 3.00 cu.in.
  • Total: 12.00 cu.in. minimum box volume required

Recommended Box Sizes for 18 AWG