Libreng calculator ng laman ng electrical box ayon sa NEC 314.16 na naglilista ng nakalaang volume para sa bawat conductor, device, clamp, grounding conductor, support fitting, at terminal block, para makalkula mo ang laman ng kahon at masuri kung sumusunod sa code ang instalasyon.

Box Fill Calculator

Calculate electrical box fill requirements per NEC 314.16

Your box & components
01 Choose your box
Box capacity— in³
02Count what’s insideWire gauge
Same wire gauge throughout, including grounds
2.25 in³ per allowance
Exclude grounds
Count mounting straps
Entering the box
Inside the box only
Updates as you edit. Grounds are counted separately.

Box Fill Calculator

Bakit Gamitin ang Aming Box Fill Calculator?

Libreng box fill calculator na nagpapakita ng buong pagkakahati ng volume ayon sa NEC 314.16, bawat bahagi, para masuri mo ang resulta at maipaliwanag ang batayan nito sa pagpaplano ng layout, inspeksiyon, o pag-aayos ng trabaho.

Na-update para sa NEC 2023

Ang aming box fill calculator ay napapanahon sa mga pinakabagong kinakailangan ng National Electrical Code kasama ang terminal blocks ayon sa 314.16(B)(6).

Instant na Resulta

Makakuha ng tumpak na box fill calculations sa ilang segundo lamang, na may detalyadong breakdown ng volume para sa bawat component.

100% Libre

Hindi kailangan mag-sign up. Gamitin ang aming box fill calculator nang libre – tumpak na kalkulasyon kapag kailangan mo.

Mobile Box Fill Calculator

Mag-calculate ng box fill sa kahit anong device – perpekto para sa on-site na kalkulasyon.

Paano Gumagana ang Box Fill Calculator

Tatlong simpleng hakbang para kalkulahin ang electrical box fill ayon sa NEC 314.16

  1. 01

    Pumili ng Uri ng Box

    Pumili mula sa mga standard na laki ng electrical box o mag-enter ng custom na dimensyon para sa iyong box fill calculation.

  2. 02

    Magdagdag ng mga Component

    I-enter ang mga conductor, device, clamp, at grounding wire para sa tumpak na box fill calculation.

  3. 03

    Makuha ang mga Resulta

    Agad na makita kung ang iyong electrical box ay nakakatugon sa mga kinakailangan ng NEC 314.16.

How to Calculate Box Fill by Hand

This worked example uses the calculator's demo setup: a 4" x 2-1/8" square box (30.30 in³) with six 12 AWG conductors, one device yoke, three entering equipment grounding conductors (EGCs) and internal cable clamps. Every allowance uses the 12 AWG volume of 2.25 in³ from Table 314.16(B).

  1. 314.16(B)(1) Conductors: 6 conductors × 2.25 in³ = 13.50 in³. Each insulated conductor that comes from outside the box and is spliced or terminated inside counts once.
  2. 314.16(B)(2) Internal cable clamps: one or more clamps count as a single allowance, 1 × 2.25 in³ = 2.25 in³.
  3. 314.16(B)(3) Support fittings (fixture studs, hickeys): none in this box, 0.00 in³. Each type present would add one allowance.
  4. 314.16(B)(4) Device yokes: one yoke counts as two allowances, 2 × 2.25 in³ = 4.50 in³.
  5. 314.16(B)(5) Equipment grounding conductors: 1 to 4 entering EGCs share one allowance, and each EGC beyond four adds one-quarter allowance. Three EGCs = 1 × 2.25 in³ = 2.25 in³ (six EGCs would be 1.5 allowances).
  6. 314.16(B)(6) Terminal blocks: none in this box, 0.00 in³.

Required volume: 13.50 + 2.25 + 0.00 + 4.50 + 2.25 + 0.00 = 22.50 in³. The box holds 30.30 in³, so the calculated fill uses 74.3% and leaves 7.80 in³. This checks box volume only; confirm the volume marked on your box and verify other installation requirements separately.

Open this example in the calculator

Box Fill Volume Allowance by Wire Size

Each counted allowance uses the volume for the conductor size in this table. Where a rule says to use the largest conductor, use that size.

Wire size (AWG)Volume per allowance (in³)Volume per allowance (cm³)
18 AWG1.5024.6
16 AWG1.7528.7
14 AWG2.0032.8
12 AWG2.2536.9
10 AWG2.5041.0
8 AWG3.0049.2
6 AWG5.0081.9

Source: NEC 2023 Table 314.16(B). Checked 2026-11-21.

Mga Madalas Itanong tungkol sa Box Fill Calculator

Ano ang electrical box fill calculation?

Ang box fill calculation ay nagtatakda kung ang isang electrical box ay may sapat na volume para sa lahat ng conductor, device, at fitting ayon sa NEC Article 314.16. Ino-automate ng aming calculator ang prosesong ito para matiyak ang ligtas na instalasyon at maiwasan ang sobrang init.

Kasama ba ang mga wire nut sa box fill calculation?

Hindi, ang mga wire nut (twist-on connector) ay hindi kasama sa box fill. Ang calculator ay nagbibilang lamang ng mga conductor, device, clamp, at equipment grounding conductor ayon sa NEC 314.16.

Paano binibilang ng calculator ang mga ground wire?

Lahat ng equipment grounding conductor sa isang box ay binibilang bilang volume ng isang conductor lamang sa box fill calculation, batay sa pinakamalaking equipment grounding conductor na pumapasok sa box ayon sa NEC 314.16(B)(5).

Paano binibilang ng calculator ang mga ground wire? (English page)

Ano ang nagbago sa NEC 2023 para sa box fill?

Idinagdag ng NEC 2023 ang 314.16(B)(6) na nag-aatas na isama ang mga terminal block sa box fill calculation. Ang aming calculator ay ganap na na-update para sa NEC 2023, na nagbibilang ng mga terminal block batay sa pinakamalaking conductor na nakakonekta.

Handa Ka Na Bang Mag-calculate ng Box Fill?

Suriin kung natutugunan ng iyong mga instalasyong elektrikal ang NEC 314.16 gamit ang aming libreng box fill calculator, kasama ang nakalaang volume para sa terminal block sa 314.16(B)(6) ng edisyong 2023.

Simulan ang Box Fill Calculator