Gratis NEC 314.16 dosfyllnadskalkylator

Dosfyllnadskalkylator för elektriker

En gratis kalkylator för dosfyllnad enligt NEC 314.16 som redovisar volymtilläggen för varje ledare, apparat, kabelklämma, skyddsledare, stödbeslag och kopplingsplint. Beräkna dosfyllnaden och kontrollera att installationen följer föreskrifterna.

Dosfyllnadskalkylator

Calculate electrical box fill requirements per NEC 314.16

Your box & components
01 Choose your box
Box capacity— in³
02Count what’s insideWire gauge
Same wire gauge throughout, including grounds
2.25 in³ per allowance
Exclude grounds
Count mounting straps
Entering the box
Inside the box only
Updates as you edit. Grounds are counted separately.

Box Fill Calculator

Varför använda vår dosfyllnadskalkylator?

En gratis dosfyllnadskalkylator som visar hela volymberäkningen enligt NEC 314.16, komponent för komponent, så att du kan kontrollera och motivera resultatet vid planering, besiktning eller omarbete.

Uppdaterad för NEC 2023

Vår dosfyllnadskalkylator följer de senaste kraven i National Electrical Code, inklusive plintblock enligt 314.16(B)(6).

Omedelbart resultat

Få exakta dosfyllnadsberäkningar på sekunder med detaljerade volymuppdelningar för varje komponent.

100 % gratis kalkylator

Ingen registrering krävs. Använd vår dosfyllnadskalkylator gratis – exakta beräkningar när du behöver dem.

Mobil dosfyllnadskalkylator

Beräkna dosfyllnad på valfri enhet – perfekt för beräkningar direkt på arbetsplatsen.

Så fungerar dosfyllnadskalkylatorn

Tre enkla steg för att beräkna dosfyllnad enligt NEC 314.16

  1. 01

    Välj dostyp

    Välj bland standardstorlekar för eldosar eller ange egna mått för din beräkning.

  2. 02

    Lägg till komponenter

    Ange ledare, apparater, klämmor och jordledare för en exakt dosfyllnadsberäkning.

  3. 03

    Se resultatet

    Se direkt om din eldosa uppfyller kraven enligt NEC 314.16.

How to Calculate Box Fill by Hand

This worked example uses the calculator's demo setup: a 4" x 2-1/8" square box (30.30 in³) with six 12 AWG conductors, one device yoke, three entering equipment grounding conductors (EGCs) and internal cable clamps. Every allowance uses the 12 AWG volume of 2.25 in³ from Table 314.16(B).

  1. 314.16(B)(1) Conductors: 6 conductors × 2.25 in³ = 13.50 in³. Each insulated conductor that comes from outside the box and is spliced or terminated inside counts once.
  2. 314.16(B)(2) Internal cable clamps: one or more clamps count as a single allowance, 1 × 2.25 in³ = 2.25 in³.
  3. 314.16(B)(3) Support fittings (fixture studs, hickeys): none in this box, 0.00 in³. Each type present would add one allowance.
  4. 314.16(B)(4) Device yokes: one yoke counts as two allowances, 2 × 2.25 in³ = 4.50 in³.
  5. 314.16(B)(5) Equipment grounding conductors: 1 to 4 entering EGCs share one allowance, and each EGC beyond four adds one-quarter allowance. Three EGCs = 1 × 2.25 in³ = 2.25 in³ (six EGCs would be 1.5 allowances).
  6. 314.16(B)(6) Terminal blocks: none in this box, 0.00 in³.

Required volume: 13.50 + 2.25 + 0.00 + 4.50 + 2.25 + 0.00 = 22.50 in³. The box holds 30.30 in³, so the calculated fill uses 74.3% and leaves 7.80 in³. This checks box volume only; confirm the volume marked on your box and verify other installation requirements separately.

Open this example in the calculator

Box Fill Volume Allowance by Wire Size

Each counted allowance uses the volume for the conductor size in this table. Where a rule says to use the largest conductor, use that size.

Wire size (AWG)Volume per allowance (in³)Volume per allowance (cm³)
18 AWG1.5024.6
16 AWG1.7528.7
14 AWG2.0032.8
12 AWG2.2536.9
10 AWG2.5041.0
8 AWG3.0049.2
6 AWG5.0081.9

Source: NEC 2023 Table 314.16(B). Checked 2026-11-21.

Vanliga frågor om dosfyllnad

Vad innebär dosfyllnadsberäkning?

Dosfyllnadsberäkning avgör om en eldosa har tillräcklig volym för alla ledare, apparater och tillbehör enligt NEC artikel 314.16. Vår kalkylator automatiserar processen för att säkerställa säkra installationer och förhindra överhettning.

Räknas kopplingshylsor i dosfyllnadsberäkningen?

Nej, kopplingshylsor räknas inte mot dosfyllnaden. Kalkylatorn räknar bara ledare, apparater, klämmor och skyddsjordledare enligt NEC 314.16.

Hur räknar kalkylatorn jordledare?

Alla skyddsjordledare i en dosa räknas som en enda ledarvolym i dosfyllnadsberäkningen, baserat på den största skyddsjordledaren som kommer in i dosan enligt NEC 314.16(B)(5).

Hur räknar kalkylatorn jordledare? (English page)

Vad ändrades i NEC 2023 för dosfyllnad?

NEC 2023 lade till 314.16(B)(6) som kräver att plintblock inkluderas i dosfyllnadsberäkningar. Vår kalkylator är fullt uppdaterad för NEC 2023 och räknar plintblock baserat på den största anslutna ledaren.