Gratis NEC 314.16 Doosvolume Calculator

Doosvolume Calculator voor Elektriciens

Een gratis calculator voor doosvulling volgens NEC 314.16 die het benodigde volume voor elke geleider, elk apparaat, elke kabelklem, aardgeleider, steunfitting en klemmenstrook afzonderlijk toont. Zo berekent u de doosvulling en controleert u of de installatie aan de voorschriften voldoet.

Doosvolume Calculator

Calculate electrical box fill requirements per NEC 314.16

Your box & components
01 Choose your box
Box capacity— in³
02Count what’s insideWire gauge
Same wire gauge throughout, including grounds
2.25 in³ per allowance
Exclude grounds
Count mounting straps
Entering the box
Inside the box only
Updates as you edit. Grounds are counted separately.

Box Fill Calculator

Waarom Onze Doosvolume Calculator?

Een gratis calculator voor doosvulling met een volledig volumeoverzicht volgens NEC 314.16, per onderdeel. Daarmee kunt u de uitkomst controleren en onderbouwen bij het ontwerp, de inspectie of herstelwerkzaamheden.

NEC 2023 Bijgewerkt

Onze calculator volgt de nieuwste eisen van het National Electrical Code, inclusief aansluitklemmen conform 314.16(B)(6).

Directe Resultaten

Krijg nauwkeurige doosvolume berekeningen in seconden, met gedetailleerde volume-uitsplitsing per component.

100% Gratis

Geen registratie nodig. Gebruik onze doosvolume calculator gratis — nauwkeurige berekeningen wanneer u ze nodig hebt.

Mobiel Beschikbaar

Bereken doosvolume op elk apparaat — ideaal voor berekeningen op de bouwplaats.

Hoe de Doosvolume Calculator Werkt

Drie eenvoudige stappen om het doosvolume te berekenen conform NEC 314.16

  1. 01

    Kies Doostype

    Kies uit standaard elektrische doosformaten of voer aangepaste afmetingen in voor de berekening.

  2. 02

    Voeg Componenten Toe

    Voer geleiders, apparaten, klemmen en aardingsdraden in voor een nauwkeurige volumeberekening.

  3. 03

    Bekijk Resultaten

    Controleer direct of uw elektrische doos voldoet aan de NEC 314.16 vullingsvereisten.

How to Calculate Box Fill by Hand

This worked example uses the calculator's demo setup: a 4" x 2-1/8" square box (30.30 in³) with six 12 AWG conductors, one device yoke, three entering equipment grounding conductors (EGCs) and internal cable clamps. Every allowance uses the 12 AWG volume of 2.25 in³ from Table 314.16(B).

  1. 314.16(B)(1) Conductors: 6 conductors × 2.25 in³ = 13.50 in³. Each insulated conductor that comes from outside the box and is spliced or terminated inside counts once.
  2. 314.16(B)(2) Internal cable clamps: one or more clamps count as a single allowance, 1 × 2.25 in³ = 2.25 in³.
  3. 314.16(B)(3) Support fittings (fixture studs, hickeys): none in this box, 0.00 in³. Each type present would add one allowance.
  4. 314.16(B)(4) Device yokes: one yoke counts as two allowances, 2 × 2.25 in³ = 4.50 in³.
  5. 314.16(B)(5) Equipment grounding conductors: 1 to 4 entering EGCs share one allowance, and each EGC beyond four adds one-quarter allowance. Three EGCs = 1 × 2.25 in³ = 2.25 in³ (six EGCs would be 1.5 allowances).
  6. 314.16(B)(6) Terminal blocks: none in this box, 0.00 in³.

Required volume: 13.50 + 2.25 + 0.00 + 4.50 + 2.25 + 0.00 = 22.50 in³. The box holds 30.30 in³, so the calculated fill uses 74.3% and leaves 7.80 in³. This checks box volume only; confirm the volume marked on your box and verify other installation requirements separately.

Open this example in the calculator

Box Fill Volume Allowance by Wire Size

Each counted allowance uses the volume for the conductor size in this table. Where a rule says to use the largest conductor, use that size.

Wire size (AWG)Volume per allowance (in³)Volume per allowance (cm³)
18 AWG1.5024.6
16 AWG1.7528.7
14 AWG2.0032.8
12 AWG2.2536.9
10 AWG2.5041.0
8 AWG3.0049.2
6 AWG5.0081.9

Source: NEC 2023 Table 314.16(B). Checked 2026-11-21.

Veelgestelde Vragen over Doosvulling

Wat is de berekening van doosvolume?

De doosvolume berekening bepaalt of een elektrische doos voldoende volume heeft voor alle geleiders, apparaten en toebehoren conform NEC Artikel 314.16. Onze calculator automatiseert dit proces voor veilige installaties en het voorkomen van oververhitting.

Tellen lasklemmen mee in de doosvolume berekening?

Nee. Lasklemmen (wire nuts) tellen niet mee in het doosvolume. De calculator telt alleen geleiders, apparaten, klemmen en aardingsgeleiders conform NEC 314.16.

Hoe worden aardingsdraden geteld bij doosvulling?

Alle aardingsgeleiders in een doos tellen als één geleidervolume, gebaseerd op de grootste aardingsgeleider die de doos binnenkomt conform NEC 314.16(B)(5).

Hoe worden aardingsdraden geteld bij doosvulling? (English page)

Wat is er veranderd in NEC 2023 voor doosvulling?

NEC 2023 heeft 314.16(B)(6) toegevoegd, waardoor aansluitklemmen moeten worden meegeteld in de doosvolume berekening. Onze calculator is volledig bijgewerkt voor NEC 2023.

Klaar om het Doosvolume te Berekenen?

Controleer met onze gratis calculator voor doosvulling of uw elektrische installaties aan NEC 314.16 voldoen, inclusief het volume voor klemmenstroken volgens 314.16(B)(6) uit de editie van 2023.

Start Doosvolume Calculator