Calculateur gratuit de remplissage de boîtes NEC 314.16

Calculateur de remplissage de boîtes électriques

Un calculateur gratuit de remplissage des boîtes électriques selon NEC 314.16, qui détaille le volume à prévoir pour chaque conducteur, appareillage, serre-câble, conducteur de mise à la terre, accessoire de support et bornier, afin de calculer le remplissage et de vérifier la conformité de l’installation.

Calculateur de remplissage de boîtes

Calculate electrical box fill requirements per NEC 314.16

Your box & components
01 Choose your box
Box capacity— in³
02Count what’s insideWire gauge
Same wire gauge throughout, including grounds
2.25 in³ per allowance
Exclude grounds
Count mounting straps
Entering the box
Inside the box only
Updates as you edit. Grounds are counted separately.

Box Fill Calculator

Pourquoi utiliser notre calculateur de remplissage de boîtes?

Un calculateur gratuit de remplissage des boîtes qui présente le détail complet des volumes selon NEC 314.16, composant par composant, pour vérifier le résultat et le justifier lors de la conception, de l’inspection ou des travaux correctifs.

Mis à jour pour le NEC 2023

Notre calculateur est à jour avec les plus récentes exigences du National Electrical Code, incluant les blocs de jonction selon le 314.16(B)(6).

Résultats instantanés

Obtenez des calculs de remplissage précis en quelques secondes, avec une ventilation détaillée du volume pour chaque composant.

100 % gratuit

Aucune inscription requise. Utilisez notre calculateur de remplissage gratuitement – des calculs précis quand vous en avez besoin.

Calculateur mobile

Calculez le remplissage de boîtes sur n'importe quel appareil – parfait pour les calculs directement sur le chantier.

Comment fonctionne le calculateur de remplissage de boîtes

Trois étapes simples pour calculer le remplissage de boîtes électriques selon le NEC 314.16

  1. 01

    Sélectionnez le type de boîte

    Choisissez parmi les dimensions standard de boîtes électriques ou entrez des dimensions personnalisées pour votre calcul.

  2. 02

    Ajoutez les composants

    Entrez les conducteurs, dispositifs, brides et fils de mise à la terre pour un calcul de remplissage précis.

  3. 03

    Obtenez les résultats

    Voyez instantanément si votre boîte électrique respecte les exigences de remplissage du NEC 314.16.

How to Calculate Box Fill by Hand

This worked example uses the calculator's demo setup: a 4" x 2-1/8" square box (30.30 in³) with six 12 AWG conductors, one device yoke, three entering equipment grounding conductors (EGCs) and internal cable clamps. Every allowance uses the 12 AWG volume of 2.25 in³ from Table 314.16(B).

  1. 314.16(B)(1) Conductors: 6 conductors × 2.25 in³ = 13.50 in³. Each insulated conductor that comes from outside the box and is spliced or terminated inside counts once.
  2. 314.16(B)(2) Internal cable clamps: one or more clamps count as a single allowance, 1 × 2.25 in³ = 2.25 in³.
  3. 314.16(B)(3) Support fittings (fixture studs, hickeys): none in this box, 0.00 in³. Each type present would add one allowance.
  4. 314.16(B)(4) Device yokes: one yoke counts as two allowances, 2 × 2.25 in³ = 4.50 in³.
  5. 314.16(B)(5) Equipment grounding conductors: 1 to 4 entering EGCs share one allowance, and each EGC beyond four adds one-quarter allowance. Three EGCs = 1 × 2.25 in³ = 2.25 in³ (six EGCs would be 1.5 allowances).
  6. 314.16(B)(6) Terminal blocks: none in this box, 0.00 in³.

Required volume: 13.50 + 2.25 + 0.00 + 4.50 + 2.25 + 0.00 = 22.50 in³. The box holds 30.30 in³, so the calculated fill uses 74.3% and leaves 7.80 in³. This checks box volume only; confirm the volume marked on your box and verify other installation requirements separately.

Open this example in the calculator

Box Fill Volume Allowance by Wire Size

Each counted allowance uses the volume for the conductor size in this table. Where a rule says to use the largest conductor, use that size.

Wire size (AWG)Volume per allowance (in³)Volume per allowance (cm³)
18 AWG1.5024.6
16 AWG1.7528.7
14 AWG2.0032.8
12 AWG2.2536.9
10 AWG2.5041.0
8 AWG3.0049.2
6 AWG5.0081.9

Source: NEC 2023 Table 314.16(B). Checked 2026-11-21.

Foire aux questions sur le calculateur de remplissage de boîtes

Qu'est-ce que le calcul de remplissage de boîtes électriques?

Le calcul de remplissage détermine si une boîte électrique possède un volume suffisant pour tous les conducteurs, dispositifs et accessoires selon l'article 314.16 du NEC. Notre calculateur automatise ce processus pour assurer des installations sécuritaires et prévenir la surchauffe.

Les marrettes comptent-elles dans le calcul de remplissage?

Non, les marrettes (connecteurs à torsion) ne comptent pas dans le remplissage de la boîte. Le calculateur ne compte que les conducteurs, les dispositifs, les brides et les conducteurs de mise à la terre selon le NEC 314.16.

Comment le calculateur compte-t-il les fils de mise à la terre?

Tous les conducteurs de mise à la terre dans une boîte comptent comme le volume d'un seul conducteur dans le calcul de remplissage, en se basant sur le plus gros conducteur de mise à la terre entrant dans la boîte selon le NEC 314.16(B)(5).

Comment le calculateur compte-t-il les fils de mise à la terre? (English page)

Qu'est-ce qui a changé dans le NEC 2023 pour le remplissage de boîtes?

Le NEC 2023 a ajouté le 314.16(B)(6) exigeant que les blocs de jonction soient inclus dans les calculs de remplissage de boîtes. Notre calculateur est entièrement mis à jour pour le NEC 2023, comptant les blocs de jonction selon le plus gros conducteur raccordé.

Prêt à calculer le remplissage de boîtes?

Vérifiez que vos installations électriques respectent NEC 314.16 grâce à notre calculateur gratuit de remplissage des boîtes, qui inclut le volume des borniers prévu par l’article 314.16(B)(6) de l’édition 2023.

Démarrer le calculateur de remplissage