Gratis NEC 314.16 dosfyldningsberegner

Dosfyldningsberegner til elektrikere

En gratis beregner til dåsefyldning efter NEC 314.16, der viser volumenbidraget for hver leder, enhed, kabelklemme, jordleder, støttebeslag og klemrække. Beregn dåsefyldningen, og kontrollér, at installationen overholder reglerne.

Dosfyldningsberegner

Calculate electrical box fill requirements per NEC 314.16

Your box & components
01 Choose your box
Box capacity— in³
02Count what’s insideWire gauge
Same wire gauge throughout, including grounds
2.25 in³ per allowance
Exclude grounds
Count mounting straps
Entering the box
Inside the box only
Updates as you edit. Grounds are counted separately.

Box Fill Calculator

Hvorfor bruge vores dosfyldningsberegner?

En gratis beregner til dåsefyldning, som viser hele volumenberegningen efter NEC 314.16, komponent for komponent, så du kan kontrollere resultatet og begrunde det ved planlægning, eftersyn eller omarbejde.

Opdateret til NEC 2023

Vores dosfyldningsberegner følger de nyeste krav i National Electrical Code, herunder klemmebokse efter 314.16(B)(6).

Øjeblikkelige resultater

Få præcise dosfyldningsberegninger på sekunder med detaljerede volumenopdelinger for hver komponent.

100 % gratis beregner

Ingen tilmelding påkrævet. Brug vores dosfyldningsberegner gratis – præcise beregninger, når du har brug for dem.

Mobil dosfyldningsberegner

Beregn dosfyldning på enhver enhed – perfekt til beregninger direkte på byggepladsen.

Sådan virker dosfyldningsberegneren

Tre enkle trin til at beregne dosfyldning efter NEC 314.16

  1. 01

    Vælg dåsetype

    Vælg blandt standardstørrelser for eldåser, eller indtast egne mål til din beregning.

  2. 02

    Tilføj komponenter

    Indtast ledere, enheder, klemmer og jordledere for en præcis dosfyldningsberegning.

  3. 03

    Se resultater

    Se med det samme, om din eldåse opfylder kravene i NEC 314.16.

How to Calculate Box Fill by Hand

This worked example uses the calculator's demo setup: a 4" x 2-1/8" square box (30.30 in³) with six 12 AWG conductors, one device yoke, three entering equipment grounding conductors (EGCs) and internal cable clamps. Every allowance uses the 12 AWG volume of 2.25 in³ from Table 314.16(B).

  1. 314.16(B)(1) Conductors: 6 conductors × 2.25 in³ = 13.50 in³. Each insulated conductor that comes from outside the box and is spliced or terminated inside counts once.
  2. 314.16(B)(2) Internal cable clamps: one or more clamps count as a single allowance, 1 × 2.25 in³ = 2.25 in³.
  3. 314.16(B)(3) Support fittings (fixture studs, hickeys): none in this box, 0.00 in³. Each type present would add one allowance.
  4. 314.16(B)(4) Device yokes: one yoke counts as two allowances, 2 × 2.25 in³ = 4.50 in³.
  5. 314.16(B)(5) Equipment grounding conductors: 1 to 4 entering EGCs share one allowance, and each EGC beyond four adds one-quarter allowance. Three EGCs = 1 × 2.25 in³ = 2.25 in³ (six EGCs would be 1.5 allowances).
  6. 314.16(B)(6) Terminal blocks: none in this box, 0.00 in³.

Required volume: 13.50 + 2.25 + 0.00 + 4.50 + 2.25 + 0.00 = 22.50 in³. The box holds 30.30 in³, so the calculated fill uses 74.3% and leaves 7.80 in³. This checks box volume only; confirm the volume marked on your box and verify other installation requirements separately.

Open this example in the calculator

Box Fill Volume Allowance by Wire Size

Each counted allowance uses the volume for the conductor size in this table. Where a rule says to use the largest conductor, use that size.

Wire size (AWG)Volume per allowance (in³)Volume per allowance (cm³)
18 AWG1.5024.6
16 AWG1.7528.7
14 AWG2.0032.8
12 AWG2.2536.9
10 AWG2.5041.0
8 AWG3.0049.2
6 AWG5.0081.9

Source: NEC 2023 Table 314.16(B). Checked 2026-11-21.

Ofte stillede spørgsmål om dosfyldning

Hvad er dosfyldningsberegning?

Dosfyldningsberegning afgør, om en eldåse har tilstrækkeligt volumen til alle ledere, enheder og tilbehør ifølge NEC artikel 314.16. Vores beregner automatiserer processen for at sikre sikre installationer og forebygge overophedning.

Tæller lederforbindere med i dosfyldningsberegningen?

Nej, lederforbindere (drejeforbindere) tæller ikke med i dosfyldningen. Beregneren tæller kun ledere, enheder, klemmer og beskyttelsesjordledere efter NEC 314.16.

Hvordan tæller beregneren jordledere?

Alle beskyttelsesjordledere i en dåse tæller som volumen af én enkelt leder i dosfyldningsberegningen, baseret på den største beskyttelsesjordleder, der føres ind i dåsen efter NEC 314.16(B)(5).

Hvordan tæller beregneren jordledere? (English page)

Hvad ændrede sig i NEC 2023 for dosfyldning?

NEC 2023 tilføjede 314.16(B)(6), som kræver, at klemmebokse medregnes i dosfyldningsberegninger. Vores beregner er fuldt opdateret til NEC 2023 og tæller klemmebokse baseret på den største tilsluttede leder.

Klar til at beregne dosfyldning?

Kontrollér, at dine elinstallationer opfylder NEC 314.16 med vores gratis beregner til dåsefyldning, inklusive volumenbidraget for klemrækker efter 314.16(B)(6) i 2023-udgaven.

Start dosfyldningsberegneren