Old Work Box 1-Gang 14 cu.in.
Cut-in box for retrofit installations in existing walls.
Quick answer
A Old Work Box 1-Gang 14 cu.in. (14 cu.in.) holds 6 × 12 AWG or 7 × 14 AWG conductors in a bare box under NEC 314.16.
Subtract two allowances for each device or strap, one for all internal clamps, one for one to four entering equipment grounding conductors plus one-quarter for each additional one (NEC 2023 314.16(B)(5)), and one for each type of support fitting. Grounding rule and edition examples →
14
cu.in. Volume
7
Max 14 AWG
6
Max 12 AWG
3" x 2" x 2-3/4"
Dimensions
Conductor Capacity per NEC 314.16
Maximum number of conductors that can fit in this box based on wire gauge (not accounting for devices, clamps, or grounds).
| Wire Gauge | Volume Each | Max Conductors* |
|---|---|---|
| 18 AWG | 1.5 cu.in. | 9 |
| 16 AWG | 1.75 cu.in. | 8 |
| 14 AWG | 2 cu.in. | 7 |
| 12 AWG | 2.25 cu.in. | 6 |
| 10 AWG | 2.5 cu.in. | 5 |
| 8 AWG | 3 cu.in. | 4 |
| 6 AWG | 5 cu.in. | 2 |
*Theoretical maximum for conductors only. Actual capacity will be less when including devices, clamps, and grounding conductors.
Common Applications
Calculate Box Fill
Use our free calculator to verify NEC 314.16 requirements.
Calculate Box Fill