Southwire publishes electrical calculation tools, including voltage-drop, cable-pulling, and conduit-fill calculators.

Southwire Calculators

Definitions and review context

A box fill calculator is a digital tool that converts conductor counts, device counts, grounding allowances, and fittings into a cubic-inch compliance check. The table below compares resource types and access methods for Southwire and BoxFillCalculator.com.

Box fill refers to the enclosure-volume accounting method in NEC 314.16. The practical difference between calculators is rarely just the final number; it is whether the tool shows the assumptions behind that number, including how it treats internal clamps, device yokes, grounding conductors, and conductor size selection.

Author: Jack Shi is the editor of Box Fill Calculator. He researches each guide against the published text of NEC Article 314.16 and cross-checks every conductor-count and box-volume figure so the guidance stays accurate and practical for electricians, inspectors, and DIY installers.

Feature Comparison

FeatureBoxFillCalculator.comSouthwire
Resource focus
NEC 314.16 box fill
Voltage drop, cable pulling, and conduit fill
Browser access
Box fill calculator (NEC 314.16)
Not listed on its calculators page (checked October 2026)
Conduit fill calculator
Re3 Conduit Fill Calculator
Smallest conduit for a mixed conductor set
Cable Pulling Calculator lists conduit size and fill percentage
Cable pulling tension and sidewall pressure
Re3 Cable Pulling Calculator
Voltage drop and wire size
Re3 Voltage Drop Calculator

Southwire box fill or Southwire conduit fill: they answer different questions

People who search for a "Southwire box fill calculator" are often looking for conduit fill, because Southwire's calculator list is built around conduit and cable rather than boxes. On the Southwire calculators page we checked in October 2026, the tools listed include a Re3 Conduit Fill Calculator (conduit fill percentage per NEC guidelines), a Re3 Cable Pulling Calculator (conduit size, fill percentage, pulling tension, sidewall pressure and jam probability) and a Re3 Voltage Drop Calculator. We did not find a box fill calculator on that page. Check the page for its current list.

Box fill and conduit fill are different calculations under different parts of the NEC. Box fill (Section 314.16) counts volume in cubic inches: every conductor, device, clamp and fitting takes an allowance, and the total must fit in the box volume. Conduit fill (NEC Chapter 9, Table 1) compares the total cross-sectional area of the conductors with a percentage of the conduit area: 53% for one conductor, 31% for two and 40% for three or more.

The questionRule behind itMeasured inSouthwire (per its calculators page)BoxFillCalculator.com
Do these devices and conductors fit in this box?NEC 314.16Cubic inchesNo box fill calculator listedBox fill calculator on the home page
What conduit size do these conductors need?NEC Chapter 9, Table 1 and Tables 4 and 5Percent of conduit areaRe3 Conduit Fill Calculator; Cable Pulling Calculator also reports conduit size and fillConduit fill calculator, with a smallest-conduit lookup for mixed conductor sets
How much voltage will this run lose?Voltage drop calculation, not a fill ruleVolts or percentRe3 Voltage Drop CalculatorNot offered
Will this cable pull without damage?Pulling calculation, not a fill ruleTension and pressureRe3 Cable Pulling CalculatorNot offered

A box fill example with the numbers shown

The numbers below were run through the same engine as our calculator. Assume a 21.0 cubic inch box and 12 AWG conductors, which carry a 2.25 cubic inch allowance each.

CaseWhat is in the boxAllowancesTotalResult in 21.0 cu in
A4 conductors, 1 device, internal clamps, grounding conductors4 conductors + 2 for the device + 1 for the clamps + 1 for all grounds = 8 allowances8 x 2.25 = 18.0 cu inFits, with 3.0 cu in spare
B6 conductors, 2 devices, internal clamps, grounding conductors6 + 4 for two devices + 1 + 1 = 12 allowances12 x 2.25 = 27.0 cu inDoes not fit; needs a larger box
  • A device counts twice the largest conductor connected to it. Internal clamps count once in total, and all equipment grounding conductors count once in total.
  • These are example inputs. Your box volume comes from the volume marked on the box or from the NEC table for its dimensions, and the conductor sizes and fittings come from your installation.

A conduit fill example from our tool

Three 12 AWG THHN conductors in 1/2 inch EMT fill about 13.1% of the conduit, well under the 40% limit for three or more conductors. For a mixed set, such as three hot conductors plus a smaller ground, the conduit fill calculator adds each conductor area and names the smallest listed size that fits. See the conduit size calculator on the conduit fill calculator page for the method.

Which tool to use

  • Use a box fill calculator when the question is whether a box is big enough. Use a conduit fill calculator when the question is conduit size.
  • Use Southwire's calculators for cable pulling, voltage drop and Southwire product selection, which are outside what this site does.
  • Whichever tool you use, confirm the result against the NEC edition and any local amendments your inspector enforces. A calculator is an aid to the code, not a replacement for it.

Related tools and guides

Frequently asked questions

Does Southwire have a box fill calculator?

We did not find one on the Southwire calculators page when we checked in October 2026. That page lists conduit fill, cable pulling and voltage drop calculators among others. Check the page for its current list.

Is conduit fill the same as box fill?

No. Box fill is a volume check in cubic inches under NEC 314.16. Conduit fill compares conductor cross-sectional area with 53%, 31% or 40% of the conduit area under NEC Chapter 9, Table 1.

What conduit fill percentages does the NEC use?

Chapter 9, Table 1 allows 53% for one conductor, 31% for two conductors and 40% for three or more conductors.

Can I use this site for conduit size?

Yes. The conduit fill calculator checks fill for one conductor size, and its smallest-conduit lookup handles mixed conductor sets for THHN in 1/2 inch to 2 inch EMT, IMC, RMC and PVC.

Why Choose Our Calculator?

Always Free

No subscriptions, no hidden fees. Use our calculator unlimited times at no cost.

No Downloads Required

Access instantly from any web browser. No app installation, no storage space needed.

NEC 2023 Ready

Updated for the latest code including terminal block requirements per 314.16(B)(6).

No Account Needed

Start calculating immediately -- no registration, login, or email required.

Try Our Free Calculator

Calculate electrical box fill per NEC 314.16 with a clear, itemized volume breakdown.

Open Calculator

Making the Right Choice

Other Comparisons